Parameter Name Default Value Range / Options Description UHS5 UNLCDHS
Detector Parameters
Walk Test LED Off On or Off
When set to On this causes a red LED to flash on the sensor when it detects
movement. Use this feature to check for adequate sensitivity levels.
Time Out
(Time adjustment)
20 minutes 0-99 minutes
Once the detector is turned on, this value sets how long the lights will stay on once
movement has ceased. Select 0 for 10 second delay use for commissioning only.
Sensitivity On 9 1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is already on. *UHS5
sets Sensitivity On and Off to the same value.
*
Sensitivity Off 9 1 (min) to 9 (max)
Sensitivity level for detecting movement when the detector is off. *UHS5 sets
Sensitivity On and Off to the same value.
*
Lux time 0 0 (disabled)
1-99 minutes
If the detector measures the lux level and decides that the output needs switching
on or off as a consequence, the lux time must elapse first. If at any time during the
timed delay the lux change reverses then the process is cancelled.
 
Power Up State On On or Off
Select No for a 30 second delay on start up. If Yes is selected, there will be no
delay on start up and the detector will always power up detecting.
 
Factory default
-
-
Restores factory default settings
User Modes
Raise
- -
Increase light level. Reverts when occupancy cycle complete.
Lower
- -
Decrease light level. Reverts when occupancy cycle complete.
Override On
- -
If the lights are off, sending the IR command will turn them on immediately and
revert to automatic operation using the manual timeout period.
Override Off
- -
If the lights are on, sending the IR command will turn them off immediately. After
the manual timeout period (described above), the sensor will revert to automatic.
Cancel
- -
Cancels the on or off override, returning the detector to normal operation.
 
Advanced programming